Posted by: DAN THE AC MAN on 2008-12-26, 14:44:29
Sounds like the high temperature limit is opening during long run cycles ...could be normal operation for your furnace,but check the filter,clean or replace it if needed....also,30 seconds sounds too short for a burner to turn off on back on due to a limit opening in most hi-eff furnaces..it usually takes at least a minute for the limit to open,then cool off and re-close ,then control board re-lights burners.....could also be a pressure switch opening during the cycle,,check the intake [if it has one] and exhaust pipe outside to make sure they are clear.......dan |